NO2 – Duct and Rough Service Nitrogen Dioxide Sensor
Configure Product:
If you can't find what you're looking for, please give us a call at +1-608-735-4800.
BAPI’s Nitrogen Dioxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations. The Duct unit samples duct air using an aspiration tube. The Rough Service unit features a ventilated BAPI-Box and is ideal for parking ramps, equipment rooms and warehouses.
The sensor has field selectable NO2 ranges of 0 to 2.5, 0 to 5, 0 to 7.5 and 0 to 10 ppm. It also has field selectable outputs of 0 to 5, 1 to 5, 0 to 10 and 2 to 10 VDC as well as a 3-wire 4 to 20 mA output. The LCD is backlight for 10 seconds after a button push.
Two independent SPDT alarm contacts switch at 5 field-selectable NO2 concentrations from 1 to 10 ppm. An alarm timer holds the output relays on for a fixed time after the NO2 level has fallen below 80% of setpoint to allow additional fan time to ensure the NO2 has been purged. The field replaceable sensor element lasts approximately 7 years and is self-tested daily.
Datasheet for Submittal
Nitrogen Dioxide (NO2) Duct and Rough Service Sensor, Datasheet for Submittal - PDFDatasheet with Pricing
Nitrogen Dioxide (NO2) Duct and Rough Service Sensor, Datasheet with Pricing - PDFInstruction Sheet
38960_Ins_NO2_BB - PDFDescription
BAPI’s Nitrogen Dioxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations. The Duct unit samples duct air using an aspiration tube. The Rough Service unit features a ventilated BAPI-Box and is ideal for parking ramps, equipment rooms and warehouses.
The sensor has field selectable NO2 ranges of 0 to 2.5, 0 to 5, 0 to 7.5 and 0 to 10 ppm. It also has field selectable outputs of 0 to 5, 1 to 5, 0 to 10 and 2 to 10 VDC as well as a 3-wire 4 to 20 mA output. The LCD is backlight for 10 seconds after a button push.
Two independent SPDT alarm contacts switch at 5 field-selectable NO2 concentrations from 1 to 10 ppm. An alarm timer holds the output relays on for a fixed time after the NO2 level has fallen below 80% of setpoint to allow additional fan time to ensure the NO2 has been purged. The field replaceable sensor element lasts approximately 7 years and is self-tested daily.