Shown below is an NIST Traceable Certificate of Calibration for a recent T1K Temperature Transmitter order.
Each transmitter is calibrated for its range using precision resistors. A Class A RTD is given a unique serial number and attached to the transmitter. The RTD is subjected to each temperature certification point and the temperature transmitter’s output is recorded at each point. BAPI normally tests at 25%, 50% and 75% of temperature span. BAPI will test at any temperature that you specify. BAPI can generate and certify temperatures between -45°C and 150°C.
If you require the temperature transmitter to be certified at more than the three standard temperatures, please contact your BAPI representative for pricing.
If you have any questions about the certification document, please contact your BAPI representative.